Inspection Report

Prepared For:
Beach Front Sample one

Property Address:
Ocean Blvd
Isle Of Palms, SC

D& I Home Inspectors, Inc.

Lawrence M. David Lic #1070
PO Box 1708
Moncks Corner, SC 29461
(843) 514-2216 www.HomeInspectorDandI.com



Date: 2/20/2006 Time: 9:00 AM Report ID: P450
Property:
Ocean Blvd
Isle Of Palms, SC
Customer:
Beach Front Sample one
Real Estate Professional:

Comment Key or Definitions

The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.

Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.

Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.

Not Present (NP) = This item, component or unit is not in this home or building.

Repair or Replace (RR) = The item, component or unit is not functioning as intended or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.

Client Is Present:
Yes

Weather:
Cloudy

Temperature:
Below 65

Rain in last 3 days:
Yes

Number of Floor Levels (Heated Space Only):
TWO LEVELS




STRUCTURAL COMPONENTS

The Home Inspector shall observe structural components including foundations, floors, walls, columns or piers, ceilings and roof. The home inspector shall describe the type of Foundation, floor structure, wall structure, columns or piers, ceiling structure, roof structure. The home inspector shall: Probe structural components where deterioration is suspected; Enter under floor crawl spaces, basements, and attic spaces except when access is obstructed, when entry could damage the property, or when dangerous or adverse situations are suspected; Report the methods used to observe under floor crawl spaces and attics; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to: Enter any area or perform any procedure that may damage the property or its components or be dangerous to or adversely effect the health of the home inspector or other persons.

Styles & Materials
FOUNDATION:
Raised Pile Foundation
METHOD USED TO OBSERVE CRAWLSPACE:
NO CRAWLSPACE
FLOOR STRUCTURE:
NOT VISIBLE
WALL STRUCTURE:
2 X 4 WOOD
COLUMNS OR PIERS:
WOOD PIERS
CEILING STRUCTURE:
6'" OR BETTER
ROOF STRUCTURE:
2 X 6 RAFTERS
2 X 8 RAFTERS
PLYWOOD
SHEATHING
ROOF-TYPE:
GABLE
METHOD USED TO OBSERVE ATTIC:
WALKED
ATTIC INFO:
PULL DOWN STAIRS
Inspection Items
1.0 Inspectors Genera Information
Comments: Inspected
Please note that photos are added to report to assist with location and to help identify problem areas. Several comments may be present in report without photos. Pleas read entire report. Do not rely on photos to show all areas of concern. We always recommend that every item or system with a comment noted in report be reviewed and repaired as needed by a lic. professional.

Many photos are taken during the inspection of a home. Some photos maynot be used in the final report. D& I attempts to keep any unused photos. These photos may be provided to the inspection client(Client Only)upon request for up to (12) twelve months after the date of inspection.


The elevator was not inspected.
1.1 FOUNDATIONS (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.)
Comments: Inspected
1.2 WALLS (Structural)
Comments: Inspected
1.3 COLUMNS OR PIERS
Comments: Inspected
1.4 FLOORS (Structural)
Comments: Inspected
1.5 CEILINGS (structural)
Comments: Inspected
Most ceiling joist/trusses are covered by insulation and are not visible for inspection.
1.6 ROOF STRUCTURE AND ATTIC
Comments: Inspected
The structure of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



EXTERIOR

The home inspector shall observe: Wall cladding, flashings, and trim; Entryway doors and a representative number of windows; Garage door operators; Decks, balconies, stoops, steps, areaways, porches and applicable railings; Eaves, soffits, and fascias; and Vegetation, grading, drainage, driveways, patios, walkways, and retaining walls with respect to their effect on the condition of the building. The home inspector shall: Describe wall cladding materials; Operate all entryway doors and a representative number of windows; Operate garage doors manually or by using permanently installed controls for any garage door operator; Report whether or not any garage door operator will automatically reverse or stop when meeting reasonable resistance during closing; and Probe exterior wood components where deterioration is suspected. The home inspector is not required to observe: Storm windows, storm doors, screening, shutters, awnings, and similar seasonal accessories; Fences; Presence of safety glazing in doors and windows; Garage door operator remote control transmitters; Geological conditions; Soil conditions; Recreational facilities (including spas, saunas, steam baths, swimming pools, tennis courts, playground equipment, and other exercise, entertainment, or athletic facilities); Detached buildings or structures; or Presence or condition of buried fuel storage tanks. The home inspector is not required to: Move personal items, panels, furniture, equipment, plant life, soil, snow, ice or debris that obstructs access or visibility.

Styles & Materials
SIDING STYLE:
LAP
SIDING MATERIAL:
WOOD
CEMENT-FIBER
TYPE OF TRIM MATERIAL:
WOOD
EXTERIOR ENTRY DOORS:
STEEL
APPURTENANCE:
DECK WITH STEPS
BALCONY
COVERED PORCH
DRIVEWAY:
CONCRETE
Inspection Items
2.0 WALL CLADDING FLASHING AND TRIM
Comments: Repair or Replace
Plywood siding is deteriated on both sides of the front balcony area. Recommend replace

2.0 Picture 1

2.0 Picture 2

Wood siding is damaged on right and left dormers, rear of home.

2.0 Picture 3

2.0 Picture 4

Wood siding is damaged along rear of screen porch area, recommend replace as needed.

2.0 Picture 5

Wood siding is damaged at upper level balcony on rear of home.

2.0 Picture 6

A few wood slats are warped or damaged around ground level, recommend repair as needed.

2.0 Picture 7

2.0 Picture 8

2.0 Picture 9

2.0 Picture 10
2.1 DOORS (Exterior)
Comments: Inspected
All exterior doors need some clean prep and paint.

2.1 Picture 1

2.1 Picture 2

2.1 Picture 3
2.2 WINDOWS
Comments: Repair or Replace
All windows have heavy rusted hinge hardware.

2.2 Picture 1

2.2 Picture 2
2.3 DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES AND APPLICABLE RAILINGS
Comments: Inspected
Minor damage is present at base of front porch columns, recommend repair as needed.

2.3 Picture 1
2.4 VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIOS, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building)
Comments: Inspected
Erosion is occurring at garage slab under both sides of home.

2.4 Picture 1

2.4 Picture 2
2.5 EAVES, SOFFITS AND FASCIAS
Comments: Repair or Replace
Corners of eves have minor damaged in several areas.

2.5 Picture 1

2.5 Picture 2

2.5 Picture 3
The exterior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



ROOFING

The home inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, chimneys, and roof penetrations; and Signs of' leaks or abnormal condensation on building components. The home inspector shall: Describe the type of roof covering materials; and Report the methods used to observe the roofing. The home inspector is not required to: Walk on the roofing; or Observe attached accessories including but not limited to solar systems, antennae, and lightning arrestors.

Styles & Materials
ROOF COVERING:
AGED
ARCHITECTURAL
CHIMNEY (exterior):
METAL FLUE PIPE
Inspection Items
3.0 ROOF COVERINGS
Comments: Repair or Replace
Several shingles are missing at top ridge around chimney, recommend this be corrected.

3.0 Picture 1

Roof shingles has several nail pops at rear of home at valley. Unable to determine if this area will leak. Recommend repair or replace as needed using a qualified person.

3.0 Picture 2
3.1 FLASHINGS
Comments: Inspected
3.2 SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS
Comments: Repair or Replace
Although plumbing vent pipe roof boots are not leaking at this time, they are nearing the end of their life cycle and will need replaced in the near future.
Both chimneys are rusted and need maintenance.

3.2 Picture 1

3.2 Picture 2
The roof of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Roof coverings and skylights can appear to be leak proof during inspection and weather conditions. Our inspection makes an attempt to find a leak but sometimes cannot. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



PLUMBING SYSTEM

The home inspector shall observe: Interior water supply and distribution system, including: piping materials, supports, and insulation; fixtures and faucets; functional flow; leaks; and cross connections; Interior drain, waste, and vent system, including: traps; drain, waste, and vent piping; piping supports and pipe insulation; leaks; and functional drainage; Hot water systems including: water heating equipment; normal operating controls; automatic safety controls; and chimneys, flues, and vents; Fuel storage and distribution systems including: interior fuel storage equipment, supply piping, venting, and supports; leaks; and Sump pumps. The home inspector shall describe: Water supply and distribution piping materials; Drain, waste, and vent piping materials; Water heating equipment; and Location of main water supply shutoff device. The home inspector shall operate all plumbing fixtures, including their faucets and all exterior faucets attached to the house, except where the flow end of the faucet is connected to an appliance. The home inspector is not required to: State the effectiveness of anti-siphon devices; Determine whether water supply and waste disposal systems are public or private; Operate automatic safety controls; Operate any valve except water closet flush valves, fixture faucets, and hose faucets; Observe: Water conditioning systems; Fire and lawn sprinkler systems; On-site water supply quantity and quality; On-site waste disposal systems; Foundation irrigation systems; Spas, except as to functional flow and functional drainage; Swimming pools; Solar water heating equipment; or Observe the system for proper sizing, design, or use of proper materials.

Styles & Materials
WATER SOURCE:
PUBLIC
PLUMBING DISTRIBUTION:
POLY
WASHER DRAIN SIZE:
2" DIAMETER
PLUMBING WASTE:
PVC
WATER HEATER POWER SOURCE:
ELECTRIC
CAPACITY:
50 GAL (2-3 PEOPLE)
MANUFACTURER:
RHEEM
Inspection Items
4.0 INTERIOR WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES
Comments: Inspected
Polybutylene plastic plumbing supply lines (PB) are installed in the subject house. Polybutylene has been used in this area for many years, but has had a higher than normal failure rate, and is no longer being widely used. Copper and Brass fittings used in later years have apparently reduced the failure rate. This subject house has copper fittings. For further details contact the Consumer Plumbing Recovery center at 1-800-392-7591 or the web at http://www.pbpipe.com
Kitchen sink is rusted under the counter, recommend replace.

4.0 Picture 1
4.1 INTERIOR DRAIN, WASTE AND VENT SYSTEMS
Comments: Inspected
4.2 HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS
Comments: Inspected
The plumbing in the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed and barely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant home waiting for closing) rust or deposits within the pipes can further clog the piping system. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



ELECTRICAL SYSTEMS

The home inspector shall observe: Service entrance conductors; Service equipment, grounding equipment, main over current device, and main and distribution panels; Amperage and voltage ratings of the service; Branch circuit conductors, their over current devices, and the compatibility of their ampacities and voltages; The operation of a representative number of installed ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls; The polarity and grounding of all receptacles within six feet of interior plumbing fixtures, and all receptacles in the garage or carport, and on the exterior of inspected structures; The operation of ground fault circuit interrupters; and Smoke detectors. The home inspector shall describe: Service amperage and voltage; Service entry conductor materials; Service type as being overhead or underground; and Location of main and distribution panels. The home inspector shall report any observed aluminum branch circuit wiring. The home inspector shall report on presence or absence of smoke detectors, and operate their test function, if accessible, except when detectors are part of a central system. The home inspector is not required to: Insert any tool, probe, or testing device inside the panels; Test or operate any over current device except ground fault circuit interrupters; Dismantle any electrical device or control other than to remove the covers of the main and auxiliary distribution panels; or Observe: Low voltage systems; Security system devices, heat detectors, or carbon monoxide detectors; Telephone, security, cable TV, intercoms, or other ancillary wiring that is not a part of the primary electrical distribution system; or Built-in vacuum equipment.

Styles & Materials
ELECTRICAL SERVICE CONDUCTORS:
BELOW GROUND
COPPER
220 VOLTS
PANEL CAPACITY:
200 AMP
100 AMP
PANEL TYPE:
CIRCUIT BREAKERS
ELEC. PANEL MANUFACTURER:
SQUARE D
BRANCH WIRE 15 and 20 AMP:
COPPER
WIRING METHODS:
ROMEX
Inspection Items
5.0 SERVICE ENTRANCE CONDUCTORS
Comments: Repair or Replace
Main ground wire is not properly connected to the ground rod at main service entrance.

5.0 Picture 1

5.0 Picture 2
5.1 SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS
Comments: Repair or Replace
Main panel box is located at washer/dryer room. Panel is missing knockouts (DANGEROUS) and sub panel has signs of rust. Further inspection is needed by a qualified licensed electrician. Recommend repair as needed.

5.1 Picture 1

5.1 Picture 2
5.2 BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE
Comments: Inspected
5.3 CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls)
Comments: Inspected
5.4 POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE
Comments: Inspected
5.5 OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS)
Comments: Repair or Replace
One GFCI (Ground Fault Circuit Interrupter) outlet at rear entry wont"Trip" when tested, needs repair. This is a safety issue that needs to be corrected. Recommend repair as needed

5.5 Picture 1
5.6 SMOKE DETECTORS
Comments: Not Inspected
Smoke detector should be tested at common hallway to bedrooms upon moving in to home.
5.7 Door Bell
Comments: Inspected
The electrical system of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Outlets were not removed and the inspection was only visual. Any outlet not accessible (behind the refrigerator for example) was not inspected or accessible. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



HEATING

The home inspector shall observe permanently installed heating systems including: Heating equipment; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The home inspector shall describe: Energy source; and Heating equipment and distribution type. The home inspector shall operate the systems using normal operating controls. The home inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The home inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.

Styles & Materials
HEAT TYPE:
HEAT PUMP (FORCED AIR)
ENERGY SOURCE:
ELECTRIC
NUMBER OF HEAT SYSTEMS (excluding wood):
THREE
HEAT SYSTEM BRAND:
GOODMAN
DUCTWORK:
INSULATED
FILTER TYPE:
DISPOSABLE
LOCATION OF EQUIPMENT:
LEFT SIDE OF HOME
IN ATTIC
UNDER HOME
Inspection Items
6.0 HEATING EQUIPMENT
Comments: Inspected
6.1 NORMAL OPERATING CONTROLS
Comments: Inspected
6.2 AUTOMATIC SAFETY CONTROLS
Comments: Inspected
6.3 HEAT DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors)
Comments: Repair or Replace
Duct pipe is enclosed in wood under the home. One section under the main level master appears to have some mold/mildew present, this may be caused by a leak in the duct pipe, recommend this be inspected further and repaired as needed.

6.3 Picture 1
6.4 PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM
Comments: Inspected
The heating system of this home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



CENTRAL AIR CONDITIONING

The home inspector shall observe: Central air conditioning and permanently installed cooling systems including: Cooling and air handling equipment; and Normal operating controls. Distribution systems including: Fans, pumps, ducts and piping, with associated supports, dampers, insulation, air filters, registers, fan-coil units; and The presence of an installed cooling source in each room. The home inspector shall describe: Energy sources; and Cooling equipment type. The home inspector shall operate the systems using normal operating controls. The home inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance The home inspector is not required to: Observe window air conditioners or operate cooling systems when weather conditions or other circumstances may cause equipment damage; Observe non-central air conditioners; or Observe the uniformity or adequacy of cool-air supply to the various rooms.

Styles & Materials
COOLING EQUIPMENT TYPE:
HEAT-PUMP
COOLING EQUIPMENT ENERGY SOURCE:
ELECTRICITY
CENTRAL AIR MANUFACTURER:
GOODMAN
NUMBER OF A/C UNITS:
THREE
LOCATION OF EQUIPMENT:
LEFT SIDE OF HOME
IN ATTIC
UNDER HOME
AGE OF EQUIPMENT:
UNDER 10 YRS.
Inspection Items
7.0 COOLING AND AIR HANDLER EQUIPMENT
Comments: Not Inspected
A/C was not tested for proper operation due to the outside air temperature is 65 degrees or less. We did not inspect this unit (S).
7.1 NORMAL OPERATING CONTROLS
Comments: Inspected
7.2 DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors)
Comments: Inspected
7.3 PRESENCE OF INSTALLED COOLING SOURCE IN EACH ROOM
Comments: Inspected
The cooling system of this home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed HVAC contractor would discover (Heating, Ventilation, and Air Conditioning). Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



INTERIORS

The home inspector shall observe: Walls, ceiling, and floors; Steps, stairways, balconies, and railings; Counters and a representative number of installed cabinets; and A representative number of doors and windows. The home inspector shall: Operate a representative number of windows and interior doors; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; Carpeting; or Draperies, blinds, or other window treatments.

Styles & Materials
CEILING MATERIALS:
SHEETROCK
WALL MATERIAL:
SHEETROCK
FLOOR COVERING(S):
CARPET
HARDWOOD T&G
TILE
INTERIOR DOORS:
HOLLOW CORE
WINDOW TYPES:
THERMAL/INSULATED
CABINETRY:
WOOD
Inspection Items
8.0 CEILINGS
Comments: Inspected
8.1 WALLS
Comments: Repair or Replace
Some water/moisture damaged is present at base of front balcony door.

8.1 Picture 1

8.1 Picture 2
8.2 FLOORS
Comments: Inspected
Wood flooring shows minor water damage at the half bath toilet area, cosmetic.

8.2 Picture 1
8.3 STEPS, STAIRWAYS, BALCONIES AND RAILINGS
Comments: Inspected
8.4 COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS
Comments: Inspected
8.5 DOORS (REPRESENTATIVE NUMBER)
Comments: Repair or Replace
Several closets are locked and not inspected.
Entry door needs adjustment at Washer/Dryer room. This is a maintenance issue and is for your information. Recommend repair or replace as needed using a qualified person.

8.5 Picture 1
8.6 WINDOWS (REPRESENTATIVE NUMBER)
Comments: Inspected
The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



INSULATION AND VENTILATION

The home inspector shall observe: Insulation and vapor retarders in unfinished spaces; Ventilation of attics and foundation areas; Kitchen, bathroom, and laundry venting systems; and the operation of any readily accessible attic ventilation fan, and, when temperature permits, the operation of any readily accessible thermostatic control. The home inspector shall describe: Insulation in unfinished spaces; and Absence of insulation in unfinished space at conditioned surfaces. The home inspector shall: Move insulation where readily visible evidence indicates the need to do so; and Move insulation where chimneys penetrate roofs, where plumbing drain/waste pipes penetrate floors, adjacent to earth filled stoops or porches, and at exterior doors. The home inspector is not required to report on: Concealed insulation and vapor retarders; or Venting equipment that is integral with household appliances.

Styles & Materials
VENTILATION:
GABLE VENTS
SOFFIT VENTS
DRYER POWER SOURCE:
22O ELECTRIC
DRYER VENT:
METAL
Inspection Items
9.0 INSULATION AND VAPOR RETARDERS (in unfinished spaces)
Comments: Inspected
9.1 VENTILATION OF ATTIC AND FOUNDATION AREAS
Comments: Inspected
Gable screens are damaged in attic.

9.1 Picture 1
9.2 VENTING SYSTEMS (Kitchens, baths and laundry)
Comments: Repair or Replace
Dryer vent pipe and range vent pipes are heavily rusted under home and need to be replaced

9.2 Picture 1

9.2 Picture 2
The insulation and ventilation of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Venting of exhaust fans or clothes dryer cannot be fully inspected and bends or obstructions can occur without being accessible or visible (behind wall and ceiling coverings). Only insulation that is visible was inspected. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.



BUILT-IN KITCHEN APPLIANCES

The home inspector shall observe and operate the basic functions of the following kitchen appliances: Permanently installed dishwasher, through its normal cycle; Range, cook top, and permanently installed oven; Trash compactor; Garbage disposal; Ventilation equipment or range hood; and Permanently installed microwave oven. The home inspector is not required to observe: Clocks, timers, self-cleaning oven function, or thermostats for calibration or automatic operation; Non built-in appliances; or Refrigeration units. The home inspector is not required to operate: Appliances in use; or Any appliance that is shut down or otherwise inoperable.

Styles & Materials
DISHWASHER:
MAYTAG
EXHAUST/RANGE HOOD:
VENTED
RANGE/OVEN:
ELECTRIC
GENERAL ELECTRIC
JENN AIR
BUILT-IN MICROWAVE:
GENERAL ELECTRIC
Inspection Items
10.0 DISHWASHER
Comments: Inspected
10.1 RANGES/OVENS/COOKTOPS
Comments: Inspected
10.2 RANGE HOOD
Comments: Inspected
10.3 FOOD WASTE DISPOSER
Comments: Inspected
10.4 MICROWAVE COOKING EQUIPMENT
Comments: Inspected
The built-in appliances of the home were inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

Prepared Using HomeGauge http://www.homegauge.com SHGI (c) 2000-2004 : Licensed To D & I Home Inspectors, Inc.



General Summary


D& I Home Inspectors, Inc.

PO Box 1708
Moncks Corner, SC 29461
(843) 514-2216 www.HomeInspectorDandI.com

Customer
Beach Front Sample one

Property Address
Ocean Blvd
Isle Of Palms, SC

The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or appear to warrant further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function, efficiency, or safety of the home. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

EXTERIOR
2.0 WALL CLADDING FLASHING AND TRIM
 Repair or Replace
 
Plywood siding is deteriated on both sides of the front balcony area. Recommend replace
 
Wood siding is damaged on right and left dormers, rear of home.
 
Wood siding is damaged along rear of screen porch area, recommend replace as needed.
 
Wood siding is damaged at upper level balcony on rear of home.
 
A few wood slats are warped or damaged around ground level, recommend repair as needed.
2.1 DOORS (Exterior)
 Inspected
 
All exterior doors need some clean prep and paint.
2.2 WINDOWS
 Repair or Replace
 
All windows have heavy rusted hinge hardware.
2.3 DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES AND APPLICABLE RAILINGS
 Inspected
 
Minor damage is present at base of front porch columns, recommend repair as needed.
2.4 VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIOS, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building)
 Inspected
 
Erosion is occurring at garage slab under both sides of home.
2.5 EAVES, SOFFITS AND FASCIAS
 Repair or Replace
 
Corners of eves have minor damaged in several areas.

ROOFING
3.0 ROOF COVERINGS
 Repair or Replace
 
Several shingles are missing at top ridge around chimney, recommend this be corrected.
 
Roof shingles has several nail pops at rear of home at valley. Unable to determine if this area will leak. Recommend repair or replace as needed using a qualified person.
3.2 SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS
 Repair or Replace
 
Although plumbing vent pipe roof boots are not leaking at this time, they are nearing the end of their life cycle and will need replaced in the near future.
 
Both chimneys are rusted and need maintenance.

PLUMBING SYSTEM
4.0 INTERIOR WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES
 Inspected
 
Kitchen sink is rusted under the counter, recommend replace.

ELECTRICAL SYSTEMS
5.0 SERVICE ENTRANCE CONDUCTORS
 Repair or Replace
 
Main ground wire is not properly connected to the ground rod at main service entrance.
5.1 SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS
 Repair or Replace
 
Main panel box is located at washer/dryer room. Panel is missing knockouts (DANGEROUS) and sub panel has signs of rust. Further inspection is needed by a qualified licensed electrician. Recommend repair as needed.
5.5 OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS)
 Repair or Replace
 
One GFCI (Ground Fault Circuit Interrupter) outlet at rear entry wont"Trip" when tested, needs repair. This is a safety issue that needs to be corrected. Recommend repair as needed

HEATING
6.3 HEAT DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors)
 Repair or Replace
 
Duct pipe is enclosed in wood under the home. One section under the main level master appears to have some mold/mildew present, this may be caused by a leak in the duct pipe, recommend this be inspected further and repaired as needed.

INTERIORS
8.1 WALLS
 Repair or Replace
 
Some water/moisture damaged is present at base of front balcony door.
8.2 FLOORS
 Inspected
 
Wood flooring shows minor water damage at the half bath toilet area, cosmetic.
8.5 DOORS (REPRESENTATIVE NUMBER)
 Repair or Replace
 
Several closets are locked and not inspected.
 
Entry door needs adjustment at Washer/Dryer room. This is a maintenance issue and is for your information. Recommend repair or replace as needed using a qualified person.

INSULATION AND VENTILATION
9.2 VENTING SYSTEMS (Kitchens, baths and laundry)
 Repair or Replace
 
Dryer vent pipe and range vent pipes are heavily rusted under home and need to be replaced


Prepared Using HomeGauge http://www.homegauge.com SHGI (c) 2000-2004 : Licensed To D & I Home Inspectors, Inc.




D & I Home Inspection Agreement
And Arbitration Clause

The address of the property is: Ocean Blvd, Isle Of Palms, SC .

Date: 2/20/2006                  Inspection Fee: 450.00 

THIS AGREEMENT made by and between  Lawrence M. David (Hereinafter “INSPECTOR”) and the undersigned (hereinafter “CLIENT”), collectively referred to herein as “the parties.”    The Parties Understand and Voluntarily Agree as follows:

1. INSPECTOR agrees to perform a visual inspection of the home/building and to provide CLIENT with a written inspection report identifying the defects that INSPECTOR both observed and deemed material.  INSPECTOR may offer comments as a courtesy, but these comments will not comprise the bargained-for report.  The report is only supplementary to the seller’s disclosure.
2. Unless otherwise inconsistent with this Agreement or not possible, INSPECTOR agrees to perform the inspection in accordance to the current Standards of Practice of the National Association of Certified Home Inspectors posted at http://www.nachi.org/sop.htm.  CLIENT understands that these standards contain certain limitations, exceptions, and exclusions.
3. The inspection and report are performed and prepared for the use of CLIENT, who gives INSPECTOR permission to discuss observations with real estate agents, owners, repairpersons, and other interested parties.  INSPECTOR accepts no responsibility for use or misinterpretation by third parties.   INSPECTOR’S inspection of the property and the accompanying report are in no way intended to be a guarantee or warranty, express or implied, regarding the future use, operability, habitability or suitability of the home/building or its components. Any and all warranties, express or implied, including warranties of merchantability and fitness for a particular purpose, are expressly excluded by this Agreement.

4.  INSPECTOR assumes no liability for the cost of repair or replacement of unreported defects or deficiencies either current or arising in the future. CLIENT acknowledges that the liability of INSPECTOR, its agents, employees, for claims or damages, costs of defense or suit, attorney’s fees and expenses and payments arising out of or related to the INSPECTOR’S negligence or breach of any obligation under this Agreement, including errors and omissions in the inspection or the report, shall be limited to liquidated damages in an amount equal to the fee paid to the INSPECTOR, and this liability shall be exclusive.  CLIENT waives any claim for consequential, exemplary, special or incidental damages or for the loss of the use of the home/building even if the CLIENT has been advised of the possibility of such damages. The parties acknowledge that the liquidated damages are not intended as a penalty but are intended (i) to reflect the fact that actual damages may be difficult and impractical to ascertain; (ii) to allocate risk among the INSPECTOR and CLIENT; and (iii) to enable the INSPECTOR to perform the inspection at the stated fee.

5. INSPECTOR does not perform engineering, architectural, plumbing, or any other job function requiring an occupational license in the jurisdiction where the inspection is taking place, unless the inspector holds a valid occupational license, in which case he/she may inform the CLIENT that he/she is so licensed, and is therefore qualified to go beyond this basic home inspection, and for additional fee, perform additional inspections beyond those within the scope of the basic home inspection.

6. In the event of a claim against INSPECTOR, CLIENT agrees to supply INSPECTOR with the following: (1) Written notification of adverse conditions within 14 days of discovery, and (2) Access to the premises.  Failure to comply with the above conditions will release INSPECTOR and its agents from any and all obligations or liability of any kind.

7. Initial X_____ Arbitration Clause: Any dispute, controversy, interpretation or claim for, but not limited to, breach of contract, any form of negligence, fraud or misrepresentation of any other theory of liability arising out of, from or related to the contract or arising out of, from related to the Inspection or Inspection Report shall be submitted to final and binding arbitrating under the rules and procedures of the Construction Arbitration Services, Inc. It is the decision of the arbitrator appointed hereunder shall be final the binding and judgment on the award may nr entered in any court of competent jurisdiction.

8. If any court declares any provision of this Agreement invalid or unenforceable, the remaining provisions will remain in effect.  This Agreement represents the entire agreement between the parties.  All prior communications are merged into this Agreement, and there are no terms or conditions other than those set forth herein.  No statement or promise of INSPECTOR or its agents shall be binding unless reduced to writing and signed by INSPECTOR.  No change or modification shall be enforceable against any party unless such change or modification is in writing and signed by the parties.  This Agreement shall be binding upon and enforceable by the parties and their heirs, executors, administrators, successors and assignees.  CLIENT shall have no cause of action against INSPECTOR after one year from the date of the inspection.

9. A non-transferable Limited Mechanical and Structural Warranty is available from American Home Warranty Company for the benefit of the client. This Limited Mechanical and Structural Warranty is specific in its language regarding coverage, deductibles, exclusions and claims. With respect to these matters (D & I Home Inspectors) hereby expressly limits its liability to the terms and conditions of the limited warranty, does not warrant nor guarantee the continued operation or condition of any items(s) systems(s or component(s) of the home and will not pay for any deductible, repair or replacement.  Please Initial__________ if you would like the Limited Mechanical and Structural Warranty ($25.00) additional Fee.

CLIENT HAS CAREFULLY READ THE FOREGOING, AGREES TO IT, AND ACKNOWLEDGES RECEIPT OF A COPY OF THIS AGREEMENT.

_______________________________
FOR INSPECTOR
_______________________________
CLIENT OR REPRESENTATIVE