Prepared For:
Multi Unit Sample
Property Address:
Multi Unit Sample
Charleston, SC
![]() |
| Date: 3/30/2006 | Time: 12:50 PM | Report ID: PS750 |
| Property: Multi Unit Sample Charleston, SC |
Customer: Multi Unit Sample |
Real Estate Professional: |
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this home or building.
Repair or Replace (RR) = The item, component or unit is not functioning as intended or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
| Age Of Home: Over 50 Years | Client Is Present: No | Weather: Clear |
| Temperature: Over 60 | Rain in last 3 days: No | Number of Floor Levels (Heated Space Only): TWO LEVELS |
| FOUNDATION: BRICK | METHOD USED TO OBSERVE CRAWLSPACE: CRAWLED DEBRIS | FLOOR STRUCTURE: WOOD JOISTS |
| WALL STRUCTURE: WOOD | COLUMNS OR PIERS: BRICK PIERS | CEILING STRUCTURE: 4" OR BETTER |
| ROOF STRUCTURE: 2X4 RAFTERS | ROOF-TYPE: GABLE | METHOD USED TO OBSERVE ATTIC: WALKED |
| ATTIC INFO: SCUTTLE HOLE |
| 1.0 | Inspectors Genera Information Comments: Inspected Please note that photos are added to report to assist with location and to help identify problem areas. Several comments may be present in report without photos. Pleas read entire report. Do not rely on photos to show all areas of concern. We always recommend that every item or system with a comment noted in report be reviewed and repaired as needed by a lic. professional. Many photos are taken during the inspection of a home. Some photos maynot be used in the final report. D& I attempts to keep any unused photos. These photos may be provided to the inspection client(Client Only)upon request for up to (12) twelve months after the date of inspection. FYI an old cistern (tank) is present under home
|
| 1.1 | FOUNDATIONS (Report
signs of abnormal or harmful water penetration into the building or
signs of abnormal or harmful condensation on building components.) Comments: Repair or Replace The foundation and framing under the left side rear addition is in very poor condition, recommend a structural engineer inspect to determine repairs.
Not all of crawlspace was inspected due to lack of safe access, under rear addition and right side (bath addition) |
| 1.2 | WALLS (Structural) Comments: POOR CONDITION The left side of rear addition to home appear to be bowed, Recommend further inspection by a Lic. Structural engineer.
Bath room addition to right side of home appears to have settled toward the home. This is visible around entrance to bath in unit B. The crawlspace in this area is very low to the ground and not accessible. The roof line in this area has a negative slope and may cause leaks
Recommend the exposed waste drain and vent lines be secured to the wall. Plywood sheathing located in storage area under rear addition is sitting on the ground and may attract termites.
|
| 1.3 | COLUMNS OR PIERS Comments: POOR CONDITION Block piers under rear addition to home are in poor condition, leaning and need additional support.
The center support column at rear addition to upper level does not appear to be adequate. Recommend additional support to prevent sagging.
Most brick columns and old fire place have dead dried out mortar, recommend this be corrected.
One column located under center left of home (hall of unit A) is falling apart and needs immediate repairs by qualified contractor.
|
| 1.4 | FLOORS (Structural) Comments: POOR CONDITION Outer band on side porch is sagging in several areas. From under the home visible damage by moisture and wood eating insects is present. Repairs are needed, recommend repairs be performed by a qualified contractor.
Several wooden post have been added under the front and center of of home, these post are just sitting on the ground are not considered a permanent support. Also wood sitting on the ground may attract wood eating insect. Recommend this be corrected by a qualified contractor.
Several areas under home have signs of termites and other wood eating insects. Recommend having the building inspected by a qualified pest control company.
Several amateur repairs are present under home using under sized materials, recommend all new materials be of equal or greater size.
|
| 1.5 | CEILINGS (structural) Comments: Inspected |
| 1.6 | ROOF STRUCTURE AND ATTIC Comments: Inspected Theold roof framing and wood slat sheathing is in ok shape but is a weak system
|
| SIDING STYLE: LAP | SIDING MATERIAL: AGED WOOD | TYPE OF TRIM MATERIAL: VINYL |
| EXTERIOR ENTRY DOORS: WOOD | APPURTENANCE: DECK WITH STEPS COVERED PORCH |
| 2.0 | WALL CLADDING FLASHING AND TRIM Comments: Inspected Wood siding at left side (facing front) deteriorated along bottom edge. Further deterioration can occur if not corrected. Recommend repair or replace as needed using a qualified person.
Some wood siding deteriation is present on the left bath room addition around drain lines and rear addition to upper level.
|
| 2.1 | DOORS (Exterior) Comments: POOR CONDITION All exterior doors (all three units) are out of square with jam, missing weather stripping and do not seal shut, heat loss is occurring at all doors.
|
| 2.2 | WINDOWS Comments: POOR CONDITION One window sill on left side of home
Most if not all windows are sealed shut and glazing in very poor condition.
|
| 2.3 | VEGETATION, GRADING,
DRAINAGE, DRIVEWAYS, PATIOS, WALKWAYS AND RETAINING WALLS (With respect
to their effect on the condition of the building) Comments: Inspected Tree limbs that are in contact with roof or hanging near walls should be trimmed.
|
| 2.4 | EAVES, SOFFITS AND FASCIAS Comments: Inspected |
| ROOF COVERING: AGED METAL | VIEWED ROOF COVERING FROM: GROUND BINOCULARS |
| 3.0 | ROOF COVERINGS Comments: Inspected |
| WATER SOURCE: PUBLIC | PLUMBING DISTRIBUTION: COPPER PEX POLY | WASHER DRAIN SIZE: 2" DIAMETER |
| PLUMBING WASTE: PVC CAST IRON (OLD) | WATER HEATER POWER SOURCE: GAS (QUICK RECOVERY) | MANUFACTURER: A.O. SMITH |
| Age of water heater: UNDER 10 YRS |
| 4.0.A | INTERIOR WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES Comments: Repair or Replace Fiberglass Tub is damaged/cracked and is leaking at time of inspection at Main bath. Repairs are needed Recommend a qualified licensed plumber repair or correct as needed.
Tub faucets loose and needs repair at Main bath. ,. Recommend repair as necessary by a qualified person.
Water pressure is low, this can be caused by several reasons. Recommend a plumber investigate further.
PEX water lines are just hanging loose under home.
|
| 4.1.A | HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS Comments: Repair or Replace Metal exhaust flue pipe for water heater (under rear addition is heavily rusted and should be replaced.
Newer gas hot water heater is just siting on some blocks in the storage area under rear of home. Recommend placing 18" off ground, installing a thermal expansion tank and securing to wall.
|
| 4.2.A | FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks) Comments: POOR CONDITION Old gas lines under home are in very poor condition, recommend repair or replace by a qualified contractor.
|
| 4.3.A | INTERIOR WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES Comments: Inspected Polybutylene plastic plumbing supply lines (PB) are installed in the crawlspace under Unit A kitchen. Polybutylene has been used in this area for many years, but has had a higher than normal failure rate, and is no longer being widely used. Copper and Brass fittings used in later years have apparently reduced the failure rate. This subject house has plastic fittings. For further details contact the Consumer Plumbing Recovery center at 1-800-392-7591 or the web at http://www.pbpipe.com
|
| PLUMBING SUPPLY: PEX | PLUMBING DISTRIBUTION: PEX | PLUMBING WASTE: PVC |
| WATER HEATER POWER SOURCE: ELECTRIC | CAPACITY: 28 Gal. | Age of water heater: UNDER 10 YRS |
| 4.0.B | INTERIOR WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES Comments: Inspected Exposed PEX water lines are present on the walls in this unit, again this is not standard, but I do not know of any problems this will cause.
|
| 4.1.B | INTERIOR DRAIN, WASTE AND VENT SYSTEMS Comments: Inspected Toilet is loose at floor at Hall Bath. ,. Recommend a qualified licensed plumber repair or correct as needed.
|
| 4.2.B | HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS Comments: Repair or Replace T&P (Test and Pressure) valve on water heater needs a 3/4 threaded pipe to extend within 6 inches of floor pan for safety. (PVC is not approved for hot water use). Recommend repair by a qualified person.
|
| WATER HEATER POWER SOURCE: ELECTRIC | CAPACITY: 30 GAL (SMALL) | Age of water heater: UNDER 10 YRS |
| 4.0.C | INTERIOR WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES Comments: Inspected Some water lines are mounted to the bedroom wall in this unit, while this is not standard, I don' know of any problems it may cause. These lines then exit the wall and enter unit B. These appear to be the hot water supply lines to unit B, because the water heater for unit B is in the attic above unit C.
|
| 4.1.C | INTERIOR DRAIN, WASTE AND VENT SYSTEMS Comments: Repair or Replace Waste line is leaking at right side at Kitchen sink. Repairs are needed to stop leaking water from damaging the cabinet bottom.. Recommend a qualified licensed plumber repair or correct as needed.
|
| 4.2.C | HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS Comments: Inspected Water heaters for both unit B and C, recommend installing thermal expansion tanks.
|
| ELECTRICAL SERVICE CONDUCTORS: OVERHEAD SERVICE COPPER | PANEL CAPACITY: 100 AMP | PANEL TYPE: CIRCUIT BREAKERS |
| ELEC. PANEL MANUFACTURER: CROUSE-HINDS | BRANCH WIRE 15 and 20 AMP: COPPER | WIRING METHODS: ROMEX |
| 5.0.A | SERVICE ENTRANCE CONDUCTORS Comments: Inspected |
| 5.1.A | SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS Comments: POOR CONDITION Recommend properly labeling panel box for safety.
Main panel box is located at bedroom. Panel circuits are not clearly labeled has a missing knock out inside box. This is for your information. Recommend repair as needed.
|
| 5.2.A | BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE Comments: Repair or Replace Several circuit breakers in main panel are of a different brand than panel manufacturer. The manufacturer requires that in order for the panel to be safe, only their brand is allowed to be used inside the panel. Even though these circuit breakers are all"UL approved," they are not approved to be used in panels of different manufacturers unless so indicated on the panel label.
|
| 5.3.A | CONNECTED DEVICES AND
FIXTURES (Observed from a representative number operation of ceiling
fans, lighting fixtures, switches and receptacles located inside the
house, garage, and on the dwelling's exterior walls) Comments: Repair or Replace Tenet says several outlets do not work around this unit. Not all outlets could be tested due to furniture, the outlet right of stove does not work. Recommend correct as needed |
| 5.4.A | OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS) Comments: POOR CONDITION GFCI outlet is a non-grounded outlet which is legal, but not as safe as a grounded GFCI at Main bath.
|
| 5.5.A | LOCATION OF MAIN AND DISTRIBUTION PANELS Comments: Inspected Main panel box is located at front bedroom. |
| ELECTRICAL SERVICE CONDUCTORS: OVERHEAD SERVICE | PANEL CAPACITY: 100 AMP | PANEL TYPE: CIRCUIT BREAKERS |
| BRANCH WIRE 15 and 20 AMP: COPPER | WIRING METHODS: ROMEX |
| 5.0.B | SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS Comments: Inspected |
| 5.1.B | CONNECTED DEVICES AND
FIXTURES (Observed from a representative number operation of ceiling
fans, lighting fixtures, switches and receptacles located inside the
house, garage, and on the dwelling's exterior walls) Comments: Repair or Replace What appears to be an old door bell is present over the entry door, it has exposed wires and wires are hot.
The outlet left of kitchen sink is missing a cover plate and had no power at time of inspection.
|
| 5.2.B | OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS) Comments: POOR CONDITION GFCI outlet is a non-grounded outlet which is legal, but not as safe as a grounded GFCI at Hall Bath.
|
| 5.3.B | SMOKE DETECTORS Comments: Inspected The smoke detectors in building should all be replaced for safety.
|
| ELECTRICAL SERVICE CONDUCTORS: OVERHEAD SERVICE COPPER | PANEL CAPACITY: 100 AMP | PANEL TYPE: CIRCUIT BREAKERS |
| BRANCH WIRE 15 and 20 AMP: COPPER | WIRING METHODS: ROMEX |
| 5.0.C | SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS Comments: Inspected |
| 5.1.C | CONNECTED DEVICES AND
FIXTURES (Observed from a representative number operation of ceiling
fans, lighting fixtures, switches and receptacles located inside the
house, garage, and on the dwelling's exterior walls) Comments: Inspected Several two pronged ungrounded outlets are still present in home.
|
| 5.2.C | OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS) Comments: Repair or Replace GFCI outlet is a non-grounded outlet which is legal, but not as safe as a grounded GFCI at Hall Bath. |
| COOLING EQUIPMENT TYPE: AIR CONDITIONER UNIT | COOLING EQUIPMENT ENERGY SOURCE: ELECTRICITY | CENTRAL AIR MANUFACTURER: CARRIER |
| NUMBER OF A/C UNITS: ONE | LOCATION OF EQUIPMENT: RIGHT SIDE OF HOME IN CLOSET |
| 6.0.A | COOLING AND AIR HANDLER EQUIPMENT Comments: Inspected |
| 6.1.A | NORMAL OPERATING CONTROLS Comments: Inspected |
| 6.2.A | DISTRIBUTION SYSTEMS
(including fans, pumps, ducts and piping, with supports, insulation,
air filters, registers, radiators, fan coil units and convectors) Comments: POOR CONDITION Ductwork appears to need cleaning |
| COOLING EQUIPMENT TYPE: AIR CONDITIONER UNIT | COOLING EQUIPMENT ENERGY SOURCE: ELECTRICITY | NUMBER OF A/C UNITS: ONE |
| LOCATION OF EQUIPMENT: IN CLOSET |
| 6.0.B | COOLING AND AIR HANDLER EQUIPMENT Comments: Inspected |
| 6.1.B | NORMAL OPERATING CONTROLS Comments: Inspected |
| 6.2.B | DISTRIBUTION SYSTEMS
(including fans, pumps, ducts and piping, with supports, insulation,
air filters, registers, radiators, fan coil units and convectors) Comments: POOR CONDITION Ductwork appears to need cleaning. |
| COOLING EQUIPMENT TYPE: AIR CONDITIONER UNIT | COOLING EQUIPMENT ENERGY SOURCE: ELECTRICITY | NUMBER OF A/C UNITS: ONE |
| LOCATION OF EQUIPMENT: IN ATTIC |
| 6.0.C | COOLING AND AIR HANDLER EQUIPMENT Comments: Inspected |
| 6.1.C | NORMAL OPERATING CONTROLS Comments: Inspected |
| 6.2.C | DISTRIBUTION SYSTEMS
(including fans, pumps, ducts and piping, with supports, insulation,
air filters, registers, radiators, fan coil units and convectors) Comments: POOR CONDITION Debris seen in vents indicates need for cleaning ducts with vacuum.
The air handler over flow pan in attic does not have a drain line, a float switch is present to help prevent against water over flowing, but I highly recommend the drain line be installed.
|
| CEILING MATERIALS: SHEETROCK | WALL MATERIAL: SHEETROCK | FLOOR COVERING(S): VINYL WOOD |
| INTERIOR DOORS: SOLID RAISED PANEL | WINDOW TYPES: AGED SINGLE PANE | CABINETRY: MELAMINE |
| COUNTERTOP: LAMINATE CULTURED MARBLE |
| 7.0.A | CEILINGS Comments: POOR CONDITION Unfinished sheetrock repairs are present in main bath.
Sheetrock on ceiling is damaged and appears to be sagging at Half 1/2 Bath. While this damage is cosmetic, the repair cost should be considered due to the amount of damage. Recommend repair or replace as needed using a qualified person.
Drywall on ceiling is damaged reveals a water stain indicating a leak did or still exists at front Bedroom. While this damage is cosmetic, the repair cost should be considered due to the amount of damage. Recommend repair or replace as needed using a qualified person.
|
| 7.1.A | WALLS Comments: Inspected Towel and tissue bars in main bath are damaged or missing.
|
| 7.2.A | FLOORS Comments: Repair or Replace The Subfloor in kitchen is very soft and appears to be damaged, this area is not visible from crawlspace. Due to the amount of softness, I recommend replacing the Subfloor
|
| 7.3.A | COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS Comments: POOR CONDITION Sink base cabinet in kitchen is pulling away from wall and veneer is pulling off of doors.
Counter tops in both baths are not mounted properly, just sitting in place.
|
| 7.4.A | DOORS (REPRESENTATIVE NUMBER) Comments: Inspected |
| 7.5.A | WINDOWS (REPRESENTATIVE NUMBER) Comments: POOR CONDITION Atleast one window is missing glass.
|
| CEILING MATERIALS: SHEETROCK PLASTER | WALL MATERIAL: SHEETROCK PLASTER | FLOOR COVERING(S): WOOD |
| INTERIOR DOORS: RAISED PANEL WOOD | WINDOW TYPES: AGED SINGLE PANE | COUNTERTOP: LAMINATE |
| 7.0.B | CEILINGS Comments: Inspected |
| 7.1.B | WALLS Comments: Repair or Replace The wall framing around the hall bath addition appears to be leaning or settleing. This appears to be a structural concern, recommend this area be inspected further by a structural engineer to determine the repairs needed.
|
| 7.2.B | FLOORS Comments: Inspected |
| 7.3.B | STEPS, STAIRWAYS, BALCONIES AND RAILINGS Comments: Inspected |
| 7.4.B | COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS Comments: Inspected Counter top in bath is not mounted properly, just sitting in place.
|
| 7.5.B | DOORS (REPRESENTATIVE NUMBER) Comments: Inspected |
| 7.6.B | WINDOWS (REPRESENTATIVE NUMBER) Comments: POOR CONDITION All windows in home are in poor condition, but the windows in the rear of unit B are deteriated.
|
| CEILING MATERIALS: SHEETROCK PLASTER | WALL MATERIAL: SHEETROCK PLASTER | FLOOR COVERING(S): VINYL WOOD |
| INTERIOR DOORS: RAISED PANEL | WINDOW TYPES: AGED SINGLE PANE |
| 7.0.C | CEILINGS Comments: Inspected |
| 7.1.C | WALLS Comments: Inspected Some stains are present on kitchen walls, tenant said it was raw eggs, FYI
|
| 7.2.C | FLOORS Comments: Inspected |
| 7.3.C | COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS Comments: Inspected |
| 7.4.C | DOORS (REPRESENTATIVE NUMBER) Comments: Inspected |
| 7.5.C | WINDOWS (REPRESENTATIVE NUMBER) Comments: POOR CONDITION Atleast one window is missing some glass.
|
| ATTIC INSULATION: NONE | R- VALUE: NONE | EXHAUST FAN TYPES: NONE |
| DRYER POWER SOURCE: 22O ELECTRIC |
| 8.0 | INSULATION AND VAPOR RETARDERS (in unfinished spaces) Comments: Not Present No insulation present in attic or crawlspace.
|
| 8.1 | VENTILATION OF ATTIC AND FOUNDATION AREAS Comments: Inspected |
| 8.2 | VENTING SYSTEMS (Kitchens, baths and laundry) Comments: POOR CONDITION The dryer vent for Unit A comes out of wall next to all three HVAC compressors. Dryer lint is built up on units. Recommend all three units be thoroughly cleaned and inspected by a qualified HVAC contractor. Also I recommend moving the dryer vent.
No ventilation or operating windows present in any of the bath rooms in building, recommend this be corrected.
|
| 9.0.A | DISHWASHER Comments: Inspected |
| 9.1.A | RANGES/OVENS/COOKTOPS Comments: Inspected |
| 9.0.B | DISHWASHER Comments: Inspected |
| 9.1.B | RANGES/OVENS/COOKTOPS Comments: Inspected |
| 9.0.C | DISHWASHER Comments: Inspected |
| 9.1.C | RANGES/OVENS/COOKTOPS Comments: Inspected |
![]() D& I Home Inspectors, Inc.
PO Box 1708 |
Customer |
Property Address |
| 1.1 | FOUNDATIONS (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.) | |
| Repair or Replace | ||
|
The foundation and framing under the left
side rear addition is in very poor condition, recommend a structural
engineer inspect to determine repairs. |
||
|
Not all of crawlspace was inspected due to lack of safe access, under rear addition and right side (bath addition) |
||
| 1.2 | WALLS (Structural) | |
| POOR CONDITION | ||
|
The left side of rear addition to home appear to be bowed, Recommend further inspection by a Lic. Structural engineer. |
||
|
Bath room addition to right side of home
appears to have settled toward the home. This is visible around
entrance to bath in unit B. The crawlspace in this area is very low to
the ground and not accessible. The roof line in this area has a
negative slope and may cause leaks |
||
|
Plywood sheathing located in storage area under rear addition is sitting on the ground and may attract termites. |
||
| 1.3 | COLUMNS OR PIERS | |
| POOR CONDITION | ||
|
Block piers under rear addition to home are in poor condition, leaning and need additional support. |
||
|
The center support column at rear
addition to upper level does not appear to be adequate. Recommend
additional support to prevent sagging. |
||
|
Most brick columns and old fire place have dead dried out mortar, recommend this be corrected. |
||
|
One column located under center left of
home (hall of unit A) is falling apart and needs immediate
repairs by qualified contractor. |
||
| 1.4 | FLOORS (Structural) | |
| POOR CONDITION | ||
|
Outer band on side porch is sagging in
several areas. From under the home visible damage by moisture and wood
eating insects is present. Repairs are needed, recommend repairs be
performed by a qualified contractor. |
||
|
Several wooden post have been added under
the front and center of of home, these post are just sitting on the
ground are not considered a permanent support. Also wood sitting
on the ground may attract wood eating insect. Recommend this be
corrected by a qualified contractor. |
||
|
Several areas under home have signs of
termites and other wood eating insects. Recommend having the building
inspected by a qualified pest control company. |
||
|
Several amateur repairs are present under
home using under sized materials, recommend all new materials be of
equal or greater size. |
||
| 2.0 | WALL CLADDING FLASHING AND TRIM | |
| Inspected | ||
|
Wood siding at left side (facing front)
deteriorated along bottom edge. Further deterioration can occur if not
corrected. Recommend repair or replace as needed using a qualified
person. |
||
|
Some wood siding deteriation is present on the left bath room addition around drain lines and rear addition to upper level. |
||
| 2.1 | DOORS (Exterior) | |
| POOR CONDITION | ||
|
All exterior doors (all three units) are
out of square with jam, missing weather stripping and do not seal shut,
heat loss is occurring at all doors. |
||
| 2.2 | WINDOWS | |
| POOR CONDITION | ||
|
One window sill on left side of home |
||
|
Most if not all windows are sealed shut and glazing in very poor condition. |
||
| 4.0.A | INTERIOR WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES | |
| Repair or Replace | ||
|
Fiberglass Tub is damaged/cracked and is
leaking at time of inspection at Main bath. Repairs are needed
Recommend a qualified licensed plumber repair or correct as needed. |
||
|
Water pressure is low, this can be caused by several reasons. Recommend a plumber investigate further. |
||
|
PEX water lines are just hanging loose under home. |
||
| 4.1.A | HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS | |
| Repair or Replace | ||
|
Metal exhaust flue pipe for water heater (under rear addition is heavily rusted and should be replaced. |
||
|
Newer gas hot water heater is just siting
on some blocks in the storage area under rear of home. Recommend
placing 18" off ground, installing a thermal expansion tank and
securing to wall. |
||
| 4.2.A | FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks) | |
| POOR CONDITION | ||
|
Old gas lines under home are in very poor condition, recommend repair or replace by a qualified contractor. |
||
| 4.0.B | INTERIOR WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES | |
| Inspected | ||
|
Exposed PEX water lines are present on
the walls in this unit, again this is not standard, but I do not know
of any problems this will cause. |
||
| 4.1.B | INTERIOR DRAIN, WASTE AND VENT SYSTEMS | |
| Inspected | ||
|
Toilet is loose at floor at Hall Bath. ,. Recommend a qualified licensed plumber repair or correct as needed. |
||
| 4.2.B | HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS | |
| Repair or Replace | ||
|
T&P (Test and Pressure) valve on
water heater needs a 3/4 threaded pipe to extend within 6 inches of
floor pan for safety. (PVC is not approved for hot water use).
Recommend repair by a qualified person. |
||
| 4.0.C | INTERIOR WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES | |
| Inspected | ||
|
Some water lines are mounted to the
bedroom wall in this unit, while this is not standard, I don' know of
any problems it may cause. These lines then exit the wall and enter
unit B. These appear to be the hot water supply lines to unit B,
because the water heater for unit B is in the attic above unit C. |
||
| 4.1.C | INTERIOR DRAIN, WASTE AND VENT SYSTEMS | |
| Repair or Replace | ||
|
Waste line is leaking at right side at
Kitchen sink. Repairs are needed to stop leaking water from damaging
the cabinet bottom.. Recommend a qualified licensed plumber repair or
correct as needed. |
||
| 4.2.C | HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS | |
| Inspected | ||
|
Water heaters for both unit B and C, recommend installing thermal expansion tanks. |
||
| 5.1.A | SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS | |
| POOR CONDITION | ||
|
Recommend properly labeling panel box for safety. |
||
|
Main panel box is located at bedroom.
Panel circuits are not clearly labeled has a missing knock out
inside box. This is for your information. Recommend repair as
needed. |
||
| 5.2.A | BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE | |
| Repair or Replace | ||
|
Several circuit breakers in main panel
are of a different brand than panel manufacturer. The manufacturer
requires that in order for the panel to be safe, only their brand is
allowed to be used inside the panel. Even though these circuit breakers
are all"UL approved," they are not approved to be used in panels of
different manufacturers unless so indicated on the panel label. |
||
| 5.3.A | CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) | |
| Repair or Replace | ||
|
Tenet says several outlets d | ||